Chi JH. J. Forensic Sci. 2011; 57(1): 246-249.

Affiliation

Department of Fire Science, Wu Feng University, 117 Jianguo Rd., Sec. 2, Minsyong, Chiayi 62153, Taiwan.

Copyright

(Copyright © 2011, American Society for Testing and Materials, Publisher John Wiley and Sons)

DOI

10.1111/j.1556-4029.2011.01948.x

PMID

22040381

Abstract

This study demonstrated the use of metallographic analysis and NIST's Fire Dynamics Simulator (FDS) program to identify the cause of an actual electrical fire. A severely carbonized steel plate and a cable with a bead were found inside a damaged switchboard from the debris of a factory fire. By metallographic analysis, the copper spatter on the steel plate was found to imply a short circuit has occurred and that this was the probable ignition source of the fire was supported by the presence of a small amount of copper oxide and by the cavities with the tree-like grain microstructures in the bead. The heat estimated to have been released per unit area of the switchboard in question (approximately 236.29 MJ/m(2)) served as key input data for applying the FDS simulation of the blaze. The simulation indicated that thermal insulation polyethylene (PE) played an important role in the rapid fire spread.