@article{ref1,
title="Extinguishment of compartment fires using portable chemical extinguishers and water",
journal="Fire safety journal",
year="1986",
author="Kokkala, M. A.",
volume="11",
number="3",
pages="201-209",
abstract="Extinguishing experiments on post-flashover room fires, using various kinds of portable extinguihers or water jets, are reported. Typically 2-3 kg of AB-type (general purpose) powders were required to put out test fires of almost 5 MW heat release rate. With water the minimum flow for extinction was 17 l/min or 7.5 g/m2 s. When halon or B-type powder was used the fire re-ignited.<p />",
language="",
issn="0379-7112",
doi="",
url="http://dx.doi.org/"
}