@article{ref1,
title="The development of the ESFR sprinkler system",
journal="Fire safety journal",
year="1988",
author="Yao, Changping",
volume="14",
number="1-2",
pages="65-73",
abstract="Recent advances in sprinkler technology research have resulted in a new approach to high-challenge storage fire protection designed to achieve early fire suppression with the ESFR automatic sprinkler system. ESFR stands for &quot;early suppression fast response&quot;. The ESFR concept depends on a proper balance of three separable factors: the sprinkler response (RTI), the actual delivered density (ADD), and the required delivered density (RDD). This presentation will include: (1) technical basis definition and methods of measurements of RTI, ADD and RDD; (2) development of the ESFR sprinkler; (3) fire test results; and (4) development of installation and approval standards.<p />",
language="",
issn="0379-7112",
doi="",
url="http://dx.doi.org/"
}