@article{ref1,
title="Performance in fire of FRP-strengthened and insulated reinforced concrete columns",
journal="Fire safety journal",
year="2012",
author="Cree, D. and Chowdhury, E.U. and Green, M.f. and Bisby, L.A. and Bénichou, N.",
volume="54",
number="",
pages="86-95",
abstract="This research investigates the fire performance of one circular and one square reinforced concrete column strengthened with a fibre reinforced polymer (FRP) wrap and covered with a unique supplemental fire protection system. An experimental full-scale fire resistance test was conducted at the National Research Council of Canada. The insulated and strengthened FRP wrapped columns were exposed to the ULC-S101 standard fire and both columns obtained fire endurance ratings of over 4 h. Details of the fire endurance experiment on both columns are described in this paper. Additionally, numerical models developed specifically for circular and square columns are validated against the experimental results.<p />",
language="",
issn="0379-7112",
doi="10.1016/j.firesaf.2012.08.006",
url="http://dx.doi.org/10.1016/j.firesaf.2012.08.006"
}