TY - JOUR PY - 1991// TI - Smoke production in the cone calorimeter and the room fire test JO - Fire safety journal A1 - Ostman, BA A1 - Tsantaridis, LD SP - 27 EP - 43 VL - 17 IS - 1 N2 - The smoke production rates for 13 different surface lining materials have been determined in the cone calorimeter at three irradiance levels: 25, 50 and 75 kW/m2. Two light systems have been used simultaneously, a helium-neon laser and a white light source, showing equal results. Different smoke parameters obtained in the cone calorimeter have been compared with those obtained in a full-scale room fire test. There seems to be a reasonable agreement which must be further studied.