TY - JOUR PY - 1988// TI - The development of the ESFR sprinkler system JO - Fire safety journal A1 - Yao, Changping SP - 65 EP - 73 VL - 14 IS - 1-2 N2 - Recent advances in sprinkler technology research have resulted in a new approach to high-challenge storage fire protection designed to achieve early fire suppression with the ESFR automatic sprinkler system. ESFR stands for "early suppression fast response". The ESFR concept depends on a proper balance of three separable factors: the sprinkler response (RTI), the actual delivered density (ADD), and the required delivered density (RDD). This presentation will include: (1) technical basis definition and methods of measurements of RTI, ADD and RDD; (2) development of the ESFR sprinkler; (3) fire test results; and (4) development of installation and approval standards.
LA - SN - 0379-7112 UR - http://dx.doi.org/ ID - ref1 ER -