TY - JOUR PY - 1973// TI - Use of ground cover materials to suppress fuel fires at airports JO - Fire technology A1 - Geyer, GB SP - 254 EP - 262 VL - 9 IS - 4 N2 - Test results showed that the use of inorganic ground cover materials in areas exposed to the hazards associated with a large fuel spill could contribute materially toward reducing the devastating effects of a major fuel fire. The test bed comprised a circular pan, 6 ft in diam and 5 in. deep, fabricated from 0. 25-in. thick steel. In the center of this pan was a vertical cylinder 5 in. long and 6 in. in diam, fabricated of 0. 375-in. wire mesh. As an aid in estimating the area of flame spread over the ground cover material during five 2-min consecutive time intervals, the surface of the pan was sectioned into areas of 0. 5 sq ft by means of a grid fabricated of 0. 125-in. diam steel rods.

LA - SN - 0015-2684 UR - http://dx.doi.org/ ID - ref1 ER -