TY - JOUR PY - 2022// TI - Structural integrity of composite floors in fire: a comparison of two large-scale experiments with varying slab reinforcement JO - Fire safety journal A1 - Ramesh, Selvarajah A1 - Choe, Lisa SP - e103669 EP - e103669 VL - 134 IS - N2 - This paper presents a comparison of two compartment fire experiments performed on the 9.1 m × 6.1 m composite floors using a full-scale two-story steel gravity frame to study the influence of slab reinforcement on the overall structural integrity. The floor specimens were designed to achieve a 2-h fire rating but had dissimilar slab reinforcement. The Test #1 specimen had steel wire reinforcement of 60 mm2/m width as the minimum permitted in the United States practice whereas the Test #2 specimen was reinforced with deformed steel bars (230 mm2/m) determined by incorporating tensile membrane action. The Test #1 specimen exhibited mid-panel slab integrity failure before reaching the specified fire rating period. However, the Test #2 specimen exhibited much smaller concrete cracks until it was heated up to 131 min and retained the post-fire residual strength at least two times greater than the design demand at ambient temperature. This unique large-scale testing demonstrated that the appropriate slab reinforcement scheme can delay the vertical deflection of the heated composite floor and maintain the structural integrity at large vertical displacements over a longer duration of fire exposure.