SAFETYLIT WEEKLY UPDATE

We compile citations and summaries of about 400 new articles every week.
RSS Feed

HELP: Tutorials | FAQ
CONTACT US: Contact info

Search Results

Journal Article

Citation

Chow WK, Li J. J. Fire Sci. 2001; 19(4): 258-283.

Copyright

(Copyright © 2001, SAGE Publishing)

DOI

10.1106/65LF-H4GA-9EW6-QF8E

PMID

unavailable

Abstract

The smoke-filling process in atria of local shopping malls was studied. The scenario of smoke spreading from a shop located adjacent to an atrium was considered. A two-layer zone model, CL-Atrium, was developed with balcony spill plume. Three plume expressions due to Thomas et al. [13], Poreh et al. [12] and NFPA-92B [11] were used and assessed. Comparison was made with simulations due to CFAST. It is found that a condition has to be satisfied for the plume expression due to Thomas et al. [13]. Further, the results on the smoke layer temperature and interface height in the atrium are similar while using the plume expressions by Poreh et al. [12] and Thomas et al. [13].


Language: en

NEW SEARCH