SAFETYLIT WEEKLY UPDATE

We compile citations and summaries of about 400 new articles every week.
RSS Feed

HELP: Tutorials | FAQ
CONTACT US: Contact info

Search Results

Journal Article

Citation

Andersson P, Holmstedt G. J. Fire Prot. Eng. 1998; 9(4): 31-50.

Copyright

(Copyright © 1998, SAGE Publishing)

DOI

10.1177/104239159800900404

PMID

unavailable

Abstract

The limitations of water mist in acting as a total flooding agent are discussed in this paper. The paper focuses on water mist consisting of droplets 1-100 μm in diameter. Water mists are very efficient as an extinguishing media if they are present in the flame. There are, however, several problems associated with introducing the water mist into the flame: the spray reaches only a short distance; small water droplets have a very short lifetime; droplets coagulate into larger droplets; large droplets hit obstacles such as walls and therefore have difficulties in being dispersed throughout the protected volume.