SAFETYLIT WEEKLY UPDATE

We compile citations and summaries of about 400 new articles every week.
RSS Feed

HELP: Tutorials | FAQ
CONTACT US: Contact info

Search Results

Journal Article

Citation

Janssens M, Tran HC. J. Fire Sci. 1992; 10(6): 528-555.

Copyright

(Copyright © 1992, SAGE Publishing)

DOI

unavailable

PMID

unavailable

Abstract

Compartment fire zone models are based on many simplifying assumptions, in particular that gases stratify in two distinct layers. Because of these assumptions, certain model output is in a form unsuitable for direct comparison to measurements made in full-scale room tests. The experimental data must first be reduced and transformed to be compatible with the model output. In this article, new techniques are described to calculate neutral plane height, vent flow rates, uniform upper and lower layer temperature and interface height from measured temperature profiles. The new calculation procedures conserve mass in the room. The procedures were used for data reduction of a series of 8 gas burner calibration room tests. The results of one of the tests are discussed in detail as an illustrative example.