SAFETYLIT WEEKLY UPDATE

We compile citations and summaries of about 400 new articles every week.
RSS Feed

HELP: Tutorials | FAQ
CONTACT US: Contact info

Search Results

Journal Article

Citation

Zou GW, Chow WK. J. Fire Prot. Eng. 2005; 15(2): 77-92.

Affiliation

Department of Building Engineering, Harbin Engineering University, Harbin, Heilongjiang, China; Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong, China, ( bewkchow@polyu.edu.hk )

Copyright

(Copyright © 2005, SAGE Publishing)

DOI

10.1177/1042391505047304

PMID

unavailable

Abstract

The new version of the fire dynamics simulator, FDS version 3.01, is verified by a series of full-scale fire tests. Experiments are carried out in a compartment similar in size to the ISO-9705 room calorimeter. Gasoline pool fires of different diameters are used to give different heat release rates. The ventilation factors of the compartment are adjusted to produce flashover. Fire-induced flow, temperature, and pressure fields in these different physical scenarios are calculated using the FDS software. The predictions for temperature and radiative heat flux of a post-flashover fire in the specific configuration tested are in reasonably good agreement with experimental results even when the flame occupies most of the room volume.