Distributed control system (DCS) is available in most of the compressor stations of cross-country pipeline systems. Programmable logic controller (PLC) is used in all the intermediate pigging (IP) stations/sectional valve (SV) stations to collect the field data and to control the remote actuated valves. This paper presents how DCS or PLC can be used for cathodic protection of gas pipelines. Virtual instrumentation (VI) software is used here for simulation and real-time implementation purpose. Analog input channels available in DCS/PLC can be used to measure pipe to soil potential (PSP) with the help of half-cell and voltage transducer. Logic blocks available in DCS can be used as low selector switch to select the lowest PSP. Proportional-integral (PI) controller available in DCS/PLC can be used for taking the controlling action. PI controller output varies the firing angle of AC phase controller. Phase controller output is rectified, filtered, and fed to the pipeline as cathodic protection current. Proposed scheme utilizes existing infrastructure to control pipeline corrosion.